9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-100
RTD input, 3-wire/4-wire systems
selectable
RKC communication
identifier
X0
Modbus
register address
ch1: 0432H (1074)
ch2: 0433H (1075)
Used to set the RTD input type (3-wire system or 4-wire system) which is used for measurement input.
Attribute:
R/W
Digits:
7 digits
Number of data:
2 (Data of each channel)
Data range:
0: 3-wire system
1: 4-wire system
Factory set value:
0
Related parameters:
Input type (P. 9-45)
This parameter is active when the instrument has RTD input.
Modbus high/low order bit conversion
RKC communication
identifier
MX
Modbus
register address
045EH (1118)
Used to set the order of data read (high or low) when double word data is used in Modbus communication.
Attribute:
R/W
Digits:
1
digit
Number of data:
1 (Data of each module)
Data range:
0: high order
low order (big endian)
1: low order
high order (little endian)
Factory set value:
1
Содержание Z-TIO-G
Страница 8: ...i 6 IMS01T28 E4 MEMO...
Страница 16: ...IMS01T28 E4 1 8 MEMO...
Страница 22: ...2 6 IMS01T28 E4 MEMO...
Страница 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Страница 52: ...5 14 IMS01T28 E4 MEMO...
Страница 82: ...7 18 IMS01T28 E4 MEMO...
Страница 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Страница 216: ...10 6 IMS01T28 E4 MEMO...
Страница 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Страница 230: ...11 14 IMS01T28 E4 MEMO...
Страница 244: ...A 4 IMS01T28 E4 MEMO...
Страница 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...