7. MODBUS
IMS01T28-E4
7-16
[Example] When performing control by calling up data in Memory area 3 of CH1
1.
The Memory area number, “3” is written to the Memory area transfer (006EH).
Data in Memory area 3 is called up to the CH1 register addresses.
CH1 register addresses
Memory area transfer
006EH
3
Memory area number, “3”
Event 1 set value (EV1)
0076H
Event 2 set value (EV2)
007AH
Event 3 set value (EV3)
007EH
Event 4 set value (EV4)
0082H
Control loop break alarm (LBA) time
0086H
LBA deadband
008AH
Set value (SV)
008EH
Proportional band
0092H
The data of memory area 3 is loaded into these register addresses
Integral time
0096H
Derivative time
009AH
Control response parameter
009EH
Manual reset
00B2H
Setting change rate limiter (up)
00B6H
Setting change rate limiter (down)
00BAH
Area soak time
00BEH
Link area number
00C2H
2.
Control of CH1 is performed by using data in the register addresses.
If the Memory area transfer (006EH and 006FH) and the Setting memory area number (0500H
and 0501H) are set to the same Memory area number, the respective data can be synchronized.
Values in the Control areas (0076H to 00C3H) become the same as those in the memory areas
(0504H to 0551H).
If data in the Control area is changed, data in the memory area is also changed.
If data in the memory area is changed, data in the Control area is also changed.
Содержание Z-TIO-G
Страница 8: ...i 6 IMS01T28 E4 MEMO...
Страница 16: ...IMS01T28 E4 1 8 MEMO...
Страница 22: ...2 6 IMS01T28 E4 MEMO...
Страница 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Страница 52: ...5 14 IMS01T28 E4 MEMO...
Страница 82: ...7 18 IMS01T28 E4 MEMO...
Страница 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Страница 216: ...10 6 IMS01T28 E4 MEMO...
Страница 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Страница 230: ...11 14 IMS01T28 E4 MEMO...
Страница 244: ...A 4 IMS01T28 E4 MEMO...
Страница 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...