9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-70
Action (high) at input error
RKC communication
identifier
WH
Modbus
register address
ch1: 024EH (590)
ch2: 024FH (591)
Action (low) at input error
RKC communication
identifier
WL
Modbus
register address
ch1: 0252H (594)
ch2: 0253H (595)
Action (high) at input error:
Use to select the action when the Measured value (PV) reaches the Input error determination point (high).
Action (low) at input error:
Use to select the action when the Measured value (PV) reaches the Input error determination point (low).
Attribute:
R/W
Digits:
1
digit
Number of data:
2 (Data of each channel)
Data range:
0: Normal control (PID control output)
1: Manipulated output value at input error
Factory set value:
Input error determination point (high): 0
Input error determination point (low): 0
Related parameters:
Input error determination point (high/low) (P. 9-48),
Manipulated output value at input error (P. 9-71)
Function:
Input Error Determination
Example: Input
range:
50.000 to +150.000
C
Input error determination point (high): 100.000
C
Input error determination point (low): 0.000
C
Action area at input error
Differential gap
(0.1 % of input span)
Input error determination point
(low)
Input error determination point
(high)
50.000
C
0.000
C
100.000
C
Manipulated output value
at input error
150.000
C
Select one of these
PID control output
Input range
(Within input scale range)
Action area at input error
Manipulated output value
at input error
Select one of these
PID control output
Auto mode
Manipulated output value (MV)
obtained by PID control
Manual mode
Manipulated output value (MV)
at manual setting
[Manipulated output action at input error]
Auto mode
Selected to the Manual mode just when determined to be at input error to output the Manipulated output value set by the
“Manipulated output value at input error.”
Manual mode
Not selected to the “Manipulated output value at input error” even if determined to be at input error.
Содержание Z-TIO-G
Страница 8: ...i 6 IMS01T28 E4 MEMO...
Страница 16: ...IMS01T28 E4 1 8 MEMO...
Страница 22: ...2 6 IMS01T28 E4 MEMO...
Страница 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Страница 52: ...5 14 IMS01T28 E4 MEMO...
Страница 82: ...7 18 IMS01T28 E4 MEMO...
Страница 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Страница 216: ...10 6 IMS01T28 E4 MEMO...
Страница 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Страница 230: ...11 14 IMS01T28 E4 MEMO...
Страница 244: ...A 4 IMS01T28 E4 MEMO...
Страница 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...