8. COMMUNICATION DATA LIST
IMS01T28-E4
8-21
8.3.2 Setting parameters exclusive to Z-TIO-G module
No. Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
1
Sensor bias
JI
CH1
CH2
0422
0423
1058
1059
7 R/W C
3.0000 to
3.0000
0.0000
2
PFF power supply
frequency
JJ CH1 0424 1060 7
R/W
M
0: 50 Hz
1: 60 Hz
2: Automatic setting
2
3
Power feed forward
(PFF) selection
JK CH1
CH2
0425
0426
1061
1062
7 R/W C 0: Unused
1: Used
0
4 Measurement
power
supply frequency
JL
CH1
0427
1063
7
RO
M
0.0 to 100.0 Hz
5
PFF input voltage
JM
CH1
0428
1064
7
RO
M
0.0 to 600.0 V
6
Reserved
0429
042A
1065
1066
7
PFF reference voltage
JP
CH1
042B
1067
7
R/W
M
0.0 to 300.0 V
Reference voltage is taken in at RUN.
0.0
8 Output
compensation
factor for PFF
reference voltage
JQ CH1
CH2
042C
042D
1068
1069
7
R/W
C
0.00 to 99.99
1.00
9 Output
compensation
captured value for
PFF reference voltage
JR CH1
CH2
042E
042F
1070
1071
7
R/W
C
0.00 to 9.99
0.00
10
PFF gain
JS
CH1
CH2
0430
0431
1072
1073
7
R/W
C
0.000 to 10.000
1.000
11 RTD
input,
3-wire/4-wire systems
selectable
X0 CH1
CH2
0432
0433
1074
1075
7 R/W C 0: 3-wire system
1: 4-wire system
0
12 Modbus
high/low
order bit conversion
MX CH1 045E 1118 1 R/W M 0: high order
low order
(big endian)
1: low order
high order
(little endian)
Valid for double word type item.
1
13 Output
adjustment
mode
bs CH1
CH2
7
R/W
*
C
0: Normal operation
1: Output adjustment 5 %
2: Output adjustment 100 %
Valid at STOP
Applicable to continuous voltage/current
outputs only.
0
14 Output
adjustment
value 5 %
bt CH1
CH2
7 R/W * C
0 to 10000
Output is adjusted to 5 %.
Settable except at STOP and except when
output adjustment mode is other than
zero.
2195
15 Output
adjustment
value 100 %
bu CH1
CH2
7 R/W * C
0 to 10000
Output is adjusted to 100 %.
Settable except at STOP and except when
output adjustment mode is other than
zero.
8405
* During RUN (control), the attribute of Engineering setting data is RO. To configure Engineering setting data, the RUN/STOP switch must
be set to STOP (control stopped).
Содержание Z-TIO-G
Страница 8: ...i 6 IMS01T28 E4 MEMO...
Страница 16: ...IMS01T28 E4 1 8 MEMO...
Страница 22: ...2 6 IMS01T28 E4 MEMO...
Страница 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Страница 52: ...5 14 IMS01T28 E4 MEMO...
Страница 82: ...7 18 IMS01T28 E4 MEMO...
Страница 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Страница 216: ...10 6 IMS01T28 E4 MEMO...
Страница 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Страница 230: ...11 14 IMS01T28 E4 MEMO...
Страница 244: ...A 4 IMS01T28 E4 MEMO...
Страница 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...