8. COMMUNICATION DATA LIST
IMS01T28-E4
8-9
8.3 Engineering Setting Data
There are two types of Engineering setting data; those common to other types of Z-TIO modules and those
exclusive to Z-TIO-G.
8.3.1 Setting data common to Z-TIO-A/B/C/D/G
No. Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
1 Input
type
XI CH1
CH2
0176
0177
374
375
7 R/W
* C RTD input Pt100
30:
50.000 to
150.000
C
31:
50.00 to
250.00
C
32:
150.00 to
150.00
C
Voltage (V) input
19: 0 to 1 V DC
Based on
model code
When not
specifying: 30
2
Display unit
PU
CH1
CH2
017A
017B
378
379
7 R/W *
C
0:
C
Use to select the temperature unit for
RTD input.
0
3
Decimal point
position
XU CH1
CH2
017E
017F
382
383
7 R/W
* C 0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
RTD input:
From 0 to 3 can be set.
V/I inputs:
Only 3 can be set (fixed).
Based on
model code
When not
specifying: 3
4
Input scale high
XV
CH1
CH2
0182
0183
386
387
7 R/W
* C RTD input:
Input scale low to Maximum
value of the
selected
input range
Voltage (V) input:
99.99 to
300.00
(However, a span is 200.00 or less.)
Varies with the setting of the decimal point
position. However, even if "3: Three
decimal places" is set, the maximum
settable decimal places are 2.
RTD input:
Maximum
value of the
selected input
range
V input:
100.00
5
Input scale low
XW
CH1
CH2
0186
0187
390
391
7 R/W
* C RTD input:
Minimum value of the selected
input range to Input scale high
Voltage (V) input:
99.99 to
300.00
(However, a span is 200.00 or less.)
Varies with the setting of the decimal point
position. However, even if "3: Three
decimal places" is set, the maximum
settable decimal places are 2.
RTD input:
Minimum
value of the
selected input
range
V input:
0.00
6
Input error
determination point
(high)
AV CH1
CH2
018A
018B
394
395
7 R/W
* C Input error determination point (low)
to (Input range high
5 % of input
span)
Varies with the setting of the decimal point
position. However, even if "3: Three
decimal places" is set, the maximum
settable decimal places are 2.
Input range
high
(5 %
of input span)
7
Input error
determination point
(low)
AW CH1
CH2
018E
018F
398
399
7 R/W
* C (Input range low
5 % of input span)
to Input error determination point
(high)
Varies with the setting of the decimal point
position. However, even if "3: Three
decimal places" is set, the maximum
settable decimal places are 2.
Input range
low
(5 %
of input span)
8 Burnout
direction
BS CH1
CH2
0192
0193
402
403
1 R/W
* C 0: Upscale
Valid only when the Voltage (V) input are
selected.
0
9
Square root extraction
XH
CH1
CH2
0196
0197
406
407
1 R/W
* C 0: Unused
1: Used
0
10 Output
assignment
(Logic output
selection function)
E0 CH1
CH2
019A
019B
410
411
1 R/W
* C 0: Control output
1: Logic output result
2: FAIL output
0
11
Energized/De-energized
(Logic output
selection function)
NA CH1
CH2
019E
019F
414
415
1 R/W
* C 0: Energized
1: De-energized
0
* During RUN (control), the attribute of Engineering setting data is RO. To configure Engineering setting data, the RUN/STOP switch must
be set to STOP (control stopped).
Continued on the next page.
Содержание Z-TIO-G
Страница 8: ...i 6 IMS01T28 E4 MEMO...
Страница 16: ...IMS01T28 E4 1 8 MEMO...
Страница 22: ...2 6 IMS01T28 E4 MEMO...
Страница 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Страница 52: ...5 14 IMS01T28 E4 MEMO...
Страница 82: ...7 18 IMS01T28 E4 MEMO...
Страница 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Страница 216: ...10 6 IMS01T28 E4 MEMO...
Страница 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Страница 230: ...11 14 IMS01T28 E4 MEMO...
Страница 244: ...A 4 IMS01T28 E4 MEMO...
Страница 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...