3. COMMUNICATION SETTINGS
IMS01T28-E4
3-3
Addresses when Z-TIO-G modules and other Z-TIO modules are joined
The maximum number of modules of the same type that can be connected is 16.
Z-TIO-G modules and Z-TIO-A/B/C/D modules are considered to be the same type, and thus when these
are joined, configure the addresses within the range 0 to F (0 to 15 decimal).
[Example]
Z-TIO-A/B/G modules and Z-TIO-C/D modules can be joined only when host communication is
used.
Addresses when Z-TIO-G modules and other Z-DIO-A modules are joined
When Z-TIO modules (Z-TIO-A/B/C/D/G) and Z-DIO-A modules are used connected in the same system
(unit), address setting can be done between 0 and F (0 to 15: hexadecimal) independently.
The maximum number of modules that can be connected in the same system is 31 when different types of
modules (Z-TIO and Z-DIO-A) are used.
[Example]
Module
address
Up to 16 modules
Module
address
Z-TIO-G: 10 modules
Z-TIO-A: 6 modules
Z-DIO-A: 15 modules
0
1
9
10 11
15
0
1
13 14
Up to 31 modules
Z-TIO-G: 5 modules
Z-TIO-A: 5 modules
Z-TIO-C: 6 modules
0
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15
Содержание Z-TIO-G
Страница 8: ...i 6 IMS01T28 E4 MEMO...
Страница 16: ...IMS01T28 E4 1 8 MEMO...
Страница 22: ...2 6 IMS01T28 E4 MEMO...
Страница 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Страница 52: ...5 14 IMS01T28 E4 MEMO...
Страница 82: ...7 18 IMS01T28 E4 MEMO...
Страница 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Страница 216: ...10 6 IMS01T28 E4 MEMO...
Страница 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Страница 230: ...11 14 IMS01T28 E4 MEMO...
Страница 244: ...A 4 IMS01T28 E4 MEMO...
Страница 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...