5. WIRING
IMS01T28-E4
5-8
When two or more SRZ units are connected (distributed arrangement)
Regardless of the number of units, a maximum of 16 SRZ Z-TIO modules and a maximum of 16
SRZ Z-DIO modules can be connected respectively. However, the maximum number of SRZ
modules that can be connected overall, including other function modules (Z-DIO and Z-CT), is
31.
Function modules (Z-TIO, Z-DIO and Z-CT) connected inside the same unit can be placed in any
position.
Host
computer
(master)
RS-485
RS-485
0
1
2
3
4
5
SRZ unit (slave)
Module address
(Slave address)
16
17
18
Z-TIO module
Z-DIO module
Internal communication line (RS-485)
Termination
resistor
Power supply (24 V DC)
6
7
8
9
10
11
SRZ unit (slave)
19
20
21
Z-TIO module
Z-DIO module
Power supply (24 V DC)
12
13
14
15
22
23
Z-DIO module
SRZ unit (salve)
Z-TIO module
Power supply (24 V DC)
RS-485
Module address
(Slave address)
Module address
(Slave address)
Internal communication line (RS-485)
Internal communication line
(RS-485)
Содержание Z-TIO-G
Страница 8: ...i 6 IMS01T28 E4 MEMO...
Страница 16: ...IMS01T28 E4 1 8 MEMO...
Страница 22: ...2 6 IMS01T28 E4 MEMO...
Страница 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Страница 52: ...5 14 IMS01T28 E4 MEMO...
Страница 82: ...7 18 IMS01T28 E4 MEMO...
Страница 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Страница 216: ...10 6 IMS01T28 E4 MEMO...
Страница 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Страница 230: ...11 14 IMS01T28 E4 MEMO...
Страница 244: ...A 4 IMS01T28 E4 MEMO...
Страница 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...