11. SPECIFICATIONS
IMS01T28-E4
11-11
Peak current suppression function
This function is effective for modules connected each other by connectors on the base.
The peak current suppression function is performed in coupled modules.
Master-slave mode
Setting range:
Address of interacting modules:
1, 0 to 99
Channel selection of interacting modules: 1 to 99
Selection switch of interacting modules:
0 (No interaction)
1 (Interact with other channels)
Bit 0: Memory area number
Bit 1: Operation mode
Bit
2:
Auto/Manual
Bit 3: Remote/Local
Bit
4:
Unused
Bit 5: Interlock release
Bit 6: Suspension of area soak time
Self-diagnostic function
Control stop:
Adjustment data error (Error code 1)
Data
back-up
error (Error code 2)
A/D conversion error (Error code 4)
Logic output data error (Error code 32)
Action stop (Error number is not displayed [Operation: Impossible]):
Power supply voltage monitoring
Watchdog
timer
Instrument status:
When a self-diagnostic error occurs: All output OFF
Display: A green lamp flashes (Control is stopped due to the self-
diagnosis)
A red lamp is on (Action is stopped due to the self-diagnosis)
Power
Power supply voltage:
21.6 to 26.4 V DC [Including power supply voltage variation]
(Rating 24 V DC)
Power consumption (at maximum load):
120 mA max. (at 24 V DC)
Rush current: 10 A or less
Содержание Z-TIO-G
Страница 8: ...i 6 IMS01T28 E4 MEMO...
Страница 16: ...IMS01T28 E4 1 8 MEMO...
Страница 22: ...2 6 IMS01T28 E4 MEMO...
Страница 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Страница 52: ...5 14 IMS01T28 E4 MEMO...
Страница 82: ...7 18 IMS01T28 E4 MEMO...
Страница 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Страница 216: ...10 6 IMS01T28 E4 MEMO...
Страница 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Страница 230: ...11 14 IMS01T28 E4 MEMO...
Страница 244: ...A 4 IMS01T28 E4 MEMO...
Страница 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...