9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-79
Proportional band limiter (high)
RKC communication
identifier
P6
Modbus
register address
ch1: 02AEH (686)
ch2: 02AFH (687)
Proportional band limiter (low)
RKC communication
identifier
P7
Modbus
register address
ch1: 02B2H (690)
ch2: 02B3H (691)
Proportional band limiter (high): Use to set the high limit value of Proportional band.
Proportional band limiter (low): Use to set the low limit value of Proportional band.
(However, Proportional band limiter (high)
Proportional band limiter (low))
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
RTD input:
0 (0.0, 0.00) to Input span (Unit:
C)
(Varies with the setting of the decimal point position.
However, even if "3: Three decimal places" is set, the maximum
settable decimal places are 2.)
Voltage (V) input: 0.00 to 300.00 % of input span
0 (0.0, 0.00): ON/OFF action
Factory set value:
Proportional band limiter (high): RTD input: Input
span
Voltage (V) input: 300.00
Proportional band limiter (low):
RTD input:
0.00
Voltage (V) input: 0.00
Related parameters:
PID/AT transfer (P. 9-13), Proportional band (P. 9-22),
Decimal point position
(P. 9-46)
Function:
The Proportional band range is restricted while the Autotuning (AT) function is
being executed.
Integral time limiter (high)
RKC communication
identifier
I6
Modbus
register address
ch1: 02B6H (694)
ch2: 02B7H (695)
Integral time limiter (low)
RKC communication
identifier
I7
Modbus
register address
ch1: 02BAH (698)
ch2: 02BBH (699)
Integral time limiter (high): Use to set the high limit value of Integral time.
Integral time limiter (low): Use to set the low limit value of Integral time.
(However, Integral time limiter (high)
Integral time limiter (low))
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
0.0 to 3000.0 seconds (0.0: PD action)
Factory set value:
Integral time limiter (high): 3000.0
Integral time limiter (low): 0.0
Related parameters:
PID/AT transfer (P. 9-13), Integral time (P. 9-23),
Integral/Derivative time decimal point position
(P. 9-68)
Function:
The Integral time range is restricted while the Autotuning (AT) function is being
executed.
If the Autotuning (AT) function is executed when the Integral time limiter (high) is set at “0.0,” P
and D values suitable to PD control are computed.
Содержание Z-TIO-G
Страница 8: ...i 6 IMS01T28 E4 MEMO...
Страница 16: ...IMS01T28 E4 1 8 MEMO...
Страница 22: ...2 6 IMS01T28 E4 MEMO...
Страница 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Страница 52: ...5 14 IMS01T28 E4 MEMO...
Страница 82: ...7 18 IMS01T28 E4 MEMO...
Страница 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Страница 216: ...10 6 IMS01T28 E4 MEMO...
Страница 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Страница 230: ...11 14 IMS01T28 E4 MEMO...
Страница 244: ...A 4 IMS01T28 E4 MEMO...
Страница 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...