7. COMMUNICATION DATA LIST
IMR01Y09-E3
70
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
211
(0x00D3)
Automatic temperature
rise dead time
31
R/W 0.1 to 1999.9 seconds
10.0
212
(0x00D4)
Automatic temperature
rise gradient data
31
R/W 0.1 to Input span/minutes
1.0
213
(0x00D5)
RUN/STOP group
31
R/W 0 to 16
(0: Group RUN/STOP function OFF)
0
214
(0x00D6)
Setting change rate limiter
unit time
31
R/W 1 to 3600 seconds
60
215
(0x00D7)
Soak time unit
31
R/W 0: 0 to 5999 minutes
1: 0 to 11999 seconds
Set the data range of Memory area soak
time monitor and Area soak time.
1
216
(0x00D8)
Setting limiter (high)
31
R/W Setting limiter (low) to Input scale high Input scale high
217
(0x00D9)
Setting limiter (low)
31
R/W Input scale low to Setting limiter (high) Input scale low
218
(0x00DA)
PV transfer function
31
R/W 0: Unused
1: Used
0
219
(0x00DB)
PV flashing display at
input error
31 R/W
Bit data
b0: Input
error
b1 to b15: Unused
Data 0:
Flashing
display
1:
Non-flashing
display
[Decimal number: 0 to 1]
0
220
(0x00DC)
Unused
•
•
•
224
(0x00E0)
225
(0x00E1)
Controller state 1
31
RO Bit data
b0: Burnout state
b1: Burnout state of feedback resistance
(FBR)
input
b2: Event 1 state
b3: Event 2 state
b4: Event 3 state
b5: Event 4 state
b6: Heater break alarm 1 (HBA1) state
b7: Heater break alarm 2 (HBA2) state
b8 to b15: Unused
Data
0: OFF 1: ON
[Decimal number: 0 to 255]
Continued on the next page.