7. COMMUNICATION DATA LIST
IMR01Y09-E3
64
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
143
(0x008F)
CT2 assignment
31
R/W 0: None
1: OUT1
2: OUT2
3: DO1
4: DO2
5: DO3
6: DO4
2
144
(0x0090)
Heater break alarm 2
(HBA2) type
31 R/W 0: Heater break alarm 2 (HBA2) type A
(Time-proportional control output)
1: Heater break alarm 2 (HBA2) type B
(Continuous control output and
time-proportional
control
output)
1
145
(0x0091)
Number of heater break
alarm 2 (HBA2) delay
times
31
R/W 0 to 255 times
5
146
(0x0092)
Hot/Cold start
31
R/W 0: Hot start 1
1: Hot start 2
2: Cold start
3: Stop start
0
147
(0x0093)
Start determination point
31
R/W 0 to Input span
(The unit is the same as input value.)
(0: Action depending on the Hot/Cold
start selection)
3 % of
input span
148
(0x0094)
External input type
31
R/W 0: Remote setting input (remote
control)
1: Intercontroller communication
cascade
control
2: Intercontroller communication
ratio
setting
When performing cascade control or
ratio setting, set the master controller to
0 (Remote control). Set slave controllers
to 1 (Cascade control) or 2 (Ratio
setting).
0
149
(0x0095)
Master channel selection
31
R/W 0 to 31
If the external input type corresponds to
“1: Cascade control” or “2: Ratio
setting,” the setting becomes valid.
0
150
(0x0096)
SV tracking
31
R/W 0: Unused
1: Used
1
Continued on the next page.