7. COMMUNICATION DATA LIST
IMR01Y09-E3
71
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
226
(0x00E2)
Controller state 2
31
RO Bit data
b0: Adjustment data error
b1: Back-up
error
b2: A/D conversion error
b3 to b4: Unused
b5: Custom data error
b6: Unused
b7: Watchdog timer error
b8: Program
error
(stack)
b9 to b10: Unused
b11: Program error (busy)
b12 to b14: Unused
b15: Controller communication error
Data
0: OFF 1: ON
[Decimal number: 0 to 35239]
227
(0x00E3)
Controller state
3 31
RO Bit data
b0: Control
STOP
b1: Control
RUN
b2: Manual
mode
*
b3: Remote
mode
*
b4 to b14: Unused
b15: Autotuning (AT)
Data
0: OFF
1: ON
[Decimal number: 0 to 32783]
* During operation in manual mode, the
manual mode of the operation mode
state monitor is set to the
“1: ON” state and the remote mode of
the same monitor is se to the
“0: OFF” state even if the parameter,
“Remote/Local transfer” is set to “1:
Remote mode.”
228
(0x00E4)
Unused
•
•
•
230
(0x00E6)
231
(0x00E7)
Comprehensive alarm
state
1
1 RO Bit data
b0: Burnout state
b1: Burnout state of feedback
resistance
(FBR)
input
b2: Event 1 state
b3: Event 2 state
b4: Event 3 state
b5: Event 4 state
b6: Heater break alarm 1 (HBA1) state
b7: Heater break alarm 2 (HBA2) state
b8 to b15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 255]
OR
of Controller state 1 (ID: 225) in all
controller
1
Valid only when Explicit message communication is used.
Continued on the next page.