7. COMMUNICATION DATA LIST
IMR01Y09-E3
57
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
101
(0x0065)
Energized/De-energized 31
R/W
Bit data
b0: DO1
b1: DO2
b2: DO3
b3: DO4
b4 to b15: Unused
Data 0:
Energized
1:
De-energized
[Decimal number: 0 to 15]
0
102
(0x0066)
Alarm (ALM) lamp
lighting condition 1
31 R/W
Bit data
b0: Event 1
b1: Event 2
b2: Event 3
b3: Event 4
b4 to b15: Unused
Data
0: ALM lamp is not lit
1: ALM lamp is lit
[Decimal number: 0 to 15]
1111
(Bit image)
103
(0x0067)
Alarm (ALM) lamp
lighting condition 2
31 R/W Bit data
b0: HBA1
b1: HBA2
b2 to b15: Unused
Data
0: ALM lamp is not lit
1: ALM lamp is lit
[Decimal number: 0 to 3]
11
(Bit image)
104
(0x0068)
Output status at STOP
mode
31 R/W Bit data
b0: Event function
b2: Transmission output
b2 to b15: Unused
Data
0: OFF
1: Action continued
0
105
(0x0069)
Unused
•
•
•
110
(0x006E)
111
(0x006F)
Transmission output type
31
R/W 0: None
1: PV
2: SV monitor
3: Deviation value
4: MV1 [heat-side]
5: MV2 [cool-side]
6: SV
7: Remote setting (RS) input value
1
Continued on the next page.