7. COMMUNICATION DATA LIST
IMR01Y09-E3
60
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
123
(0x007B)
Event 2 differential gap
31
R/W
Deviation, process or set value:
0 to Input span (Unit:
°
C [
°
F])
MV: 0.0 to 110.0 %
: TC/RTD:
2
°
C [
°
F]
V/I:
0.2
%
: 0.2 %
124
(0x007C)
Event 2 delay timer
31
R/W 0.0 to 600.0 seconds
0.0
125
(0x007D)
Force ON of Event 2
action
31 R/W Bit data
b0: Event output turned on at input error
occurrence
b1: Event output turned on in manual
mode
b2: Event output turned on during the
autotuning (AT) function is being
executed
b3: Event output turned on during the
setting change rate limiter is being
operated
b4 to b15: Unused
Data
0: Invalid
1: Valid
[Decimal number: 0 to 15]
0
126
(0x007E)
Event 3 type
31
R/W 0: None
1: Deviation
high
1
2: Deviation
low
1
3: Deviation
high/low
1
4: Band
1
5: Process high
1
6: Process
low
1
7: SV
high
8: SV
low
9: Unused
10: MV1 high [heat-side]
1,
2
11: MV1 low [heat-side]
1,
2
12: MV2 high [cool-side]
1
13: MV2 low [cool-side]
1
1
Event hold action is available.
2
If there is feedback resistance (FBR)
input in position proportioning
control, set to the feedback resistance
(FBR) input value.
Depends on
model code.
When not
specifying: 0
Continued on the next page.