7. COMMUNICATION DATA LIST
IMR01Y09-E3
51
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
61
(0x003D)
Heater melting
determination point 1
31 R/W 0.0 to 100.0 % of HBA1 set value
(0.0: Heater melting determination is
invalid)
If there is no current transformer 1 (CT1)
or CT1 is assigned to “0: None,” set to RO
(Only reading data is possible).
If Heater break alarm 1 (HBA1)
corresponds to “0: Type A,” set to RO
(Only reading data is possible).
30.0
62
(0x003E)
Heater break alarm 2
(HBA2) set value
31
R/W When CT is CTL-6-P-N:
0.0 to 30.0 A (0.0: Not used)
When CT is CTL-12-S56-10L-N:
0.0 to 100.0 A (0.0: Not used)
If there is no current transformer 2 (CT2)
or CT2 is assigned to “0: None,” set to RO
(Only reading data is possible).
0.0
63
(0x003F)
Heater break
determination point 2
31 R/W 0.0 to 100.0 % of HBA2 set value
(0.0: Heater break determination is
invalid)
If there is no current transformer 2 (CT2)
or CT2 is assigned to “0: None,” set to RO
(Only reading data is possible).
If Heater break alarm 2 (HBA2)
corresponds to “0: Type A,” set to RO
(Only reading data is possible).
30.0
64
(0x0040)
Heater melting
determination point 2
31 R/W 0.0 to 100.0 % of HBA2 set value
(0.0: Heater melting determination is
invalid)
If there is no current transformer 2 (CT2)
or CT2 is assigned to “0: None,” set to RO
(Only reading data is possible).
If Heater break alarm 2 (HBA2)
corresponds to “0: Type A,” set to RO
(Only reading data is possible).
30.0
65
(0x0041)
PV bias
31
R/W
−
Input span to +Input span
0
66
(0x0042)
PV digital filter
31
R/W 0.0 to 100.0 seconds
(0.0: Unused)
0.0
67
(0x0043)
PV ratio
31
R/W 0.500 to 1.500
1.000
68
(0x0044)
PV low input cut-off
31
R/W 0.00 to 25.00 % of input span
If the Input square root extraction
corresponds to “0: Unused,” set to RO
(Only reading data is possible).
0.00
Continued on the next page.