7. COMMUNICATION DATA LIST
IMR01Y09-E3
49
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
48
(0x0030)
Derivative time
[heat-side]
★
31 R/W 0 to 3600 seconds or
0.0 to 1999.9 seconds
(0, 0.0: PI action)
Varies with the setting of the
integral/derivative time decimal point
position selection.
60
49
(0x0031)
Control response
parameter
★
31 R/W 0: Slow
1: Medium
2: Fast
[P or PD action: 2 (Fast) fixed]
PID control
,
Position
proportioning
control: 0
Heat/cool PID
control: 2
50
(0x0032)
Proportional band
[cool-side]
★
31 R/W TC/RTD inputs:
1 to Input span, 0.1 to Input span or
0.01 to Input span (Unit:
°
C [
°
F])
Varies with the setting of the decimal
point position selection.
Voltage (V)/current (I) inputs:
0.1 to 1000.0 % of Input span
If control is other than heat/cool PID
control, set to RO (Only reading data is
possible).
TC/RTD: 30
V/I: 30.0
51
(0x0033)
Integral time
[cool-side]
★
31 R/W 0 to 3600 seconds or
0.0 to 1999.9 seconds (0, 0.0: PD action) *
* When the heat-side or cool-side integral
time is set to zero for heat/cool PID
control, PD action will take place for both
heat-side and cool-side.
Varies with the setting of the
integral/derivative time decimal point
position selection.
If control is other than heat/cool PID
control, set to RO (Only reading data is
possible).
240
52
(0x0034)
Derivative time
[cool-side]
★
31 R/W 0 to 3600 seconds or
0.0 to 1999.9 seconds (0, 0.0: PI action)
Varies with the setting of the
integral/derivative time decimal point
position selection.
If control is other than heat/cool PID
control, set to RO (Only reading data is
possible).
60
★
: Data related to multi-memory area function
It is possible to change only the data of the control area which is selected by the memory area
transfer (ID: 37).
Continued on the next page.