7. COMMUNICATION DATA LIST
IMR01Y09-E3
48
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
39
(0x0027)
Event 1 set value (EV1)
★
31 R/W
50
40
(0x0028)
Event 2 set value (EV2)
★
31 R/W
50
41
(0x0029)
Event 3 set value (EV3)
★
31 R/W
50
42
(0x002A)
Event 4 set value (EV4)
★
31 R/W
Deviation:
−
Input span to +Input span
Process and set value:
Input scale low to Input scale high
Manipulated output value (MV1 or
MV2):
−
5.0 to +105.0 %
If the Event type corresponds to “0:
None,” set to RO (Only reading data is
possible).
If Event 4 corresponds to “9: Control
loop break alarm (LBA),” the Event 4 set
value becomes RO (Only reading data is
possible).
50
43
(0x002B)
Control loop break alarm
(LBA) time
★
31 R/W 0 to 7200 seconds
(0: Unused)
If Event 4 is other than “9: Control loop
break alarm (LBA),” set to RO (Only
reading data is possible).
480
44
(0x002C)
LBA deadband
★
31
R/W 0 to Input span
If Event 4 is other than “9: Control loop
break alarm (LBA),” set to RO (Only
reading data is possible).
0
45
(0x002D)
Set value (SV)
★
31
R/W Setting limiter (low) to Setting limiter
(high)
TC/RTD:
0
°
C [
°
F]
V/I: 0.0 %
46
(0x002E)
Proportional band
[heat-side]
★
31 R/W TC/RTD inputs:
0 to Input span, 0.0 to Input span or
0.00 to Input span (Unit:
°
C [
°
F])
Varies with the setting of the decimal
point position selection.
Voltage (V)/current (I) inputs:
0.0 to 1000.0 % of Input span
(0, 0.0, 0.00: ON/OFF action)
TC/RTD: 30
V/I: 30.0
47
(0x002F)
Integral time
[heat-side]
★
31 R/W PID control or heat/cool PID control:
0 to 3600 seconds or
0.0 to 1999.9 seconds
(0, 0.0: PD action) *
Position proportioning control:
1 to 3600 seconds or
0.1 to 1999.9 seconds
* When the heat-side or cool-side integral
time is set to zero for heat/cool PID
control, PD action will take place for both
heat-side and cool-side.
Varies with the setting of the
integral/derivative time decimal point
position selection.
240
★
: Data related to multi-memory area function
It is possible to change only the data of the control area which is selected by the memory area
transfer (ID: 37).
Continued on the next page.