7. COMMUNICATION DATA LIST
IMR01Y09-E3
50
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
53
(0x0035)
Overlap/Deadband
★
31
R/W TC/RTD inputs:
−
Input span to +Input span
(Unit:
°
C [
°
F])
Voltage (V)/current (I) inputs:
−
100.0 to +100.0 % of Input span
Minus (
−
) setting results in overlap.
However, the overlapping range is
within the proportional range.
If control is other than heat/cool PID
control, set to RO (Only reading data is
possible).
0
54
(0x0036)
Manual reset
★
31
R/W
−
100.0 to +100.0 %
The offset can be manually eliminated.
If the integral function is valid, set to RO
(Only reading data is possible).
0.0
55
(0x0037)
Setting change rate limiter
(up)
★
31 R/W 0 to Input span/unit time *
(0: Unused)
0
56
(0x0038)
Setting change rate limiter
(down)
★
31 R/W * Unit time: 60 seconds
(factory
set
value)
0
57
(0x0039)
Area soak time
★
31
R/W 0 to 11999 seconds or
0 to 5999 minutes
Data range of Area soak time can be
selected on the Soak time unit.
0
58
(0x003A)
Link area number
★
31
R/W 0 to 8
(0: No link)
0
59
(0x003B)
Heater break alarm 1
(HBA1) set value
31 R/W When CT is CTL-6-P-N:
0.0 to 30.0 A (0.0: Not used)
When CT is CTL-12-S56-10L-N:
0.0 to 100.0 A (0.0: Not used)
If there is no current transformer 1 (CT1)
or CT1 is assigned to “0: None,” set to RO
(Only reading data is possible).
0.0
60
(0x003C)
Heater break
determination point 1
31 R/W 0.0 to 100.0 % of HBA1 set value
(0.0: Heater break determination is
invalid)
If there is no current transformer 1 (CT1)
or CT1 is assigned to “0: None,” set to RO
(Only reading data is possible).
If Heater break alarm 1 (HBA1)
corresponds to “0: Type A,” set to RO
(Only reading data is possible).
30.0
★
: Data related to multi-memory area function
It is possible to change only the data of the control area which is selected by the memory area
transfer (ID: 37).
Continued on the next page.