7. COMMUNICATION DATA LIST
IMR01Y09-E3
46
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
17
(0x0011)
Digital input (DI) state
monitor
31 RO Bit data
b0: The state of DI1
b1: The state of DI2
b2: The state of DI3
b3: The state of DI4
b4: The state of DI5
b5: The state of DI6
b6: The state of DI7
b7 to b15: Unused
Data
0: Contact open
1: Contact closed
[Decimal number: 0 to 127]
18
(0x0012)
Output state monitor
31
RO Bit data
b0: The state of OUT1
b1: The state of OUT2
b2: The state of DO1
b3: The state of DO2
b4: The state of DO3
b5: The state of DO4
b6 to b15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 63]
19
(0x0013)
Operation mode state
monitor
31 RO Bit data
b0: Control STOP
b1: Control RUN
b2: Manual mode *
b3: Remote mode *
b4 to b15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 15]
* During operation in manual mode, the
manual mode of the operation mode
state monitor is set to the “1: ON”
state and the remote mode of the same
monitor is se to the “0: OFF” state
even if the parameter, “Remote/Local
transfer” is set to “1: Remote mode.”
20
(0x0014)
Memory area soak time
monitor
31 RO 0 to 11999 seconds or
0 to 5999 minutes
Data range of Area soak time can be
selected on the Soak time unit.
21
(0x0015)
Integrated operating time
monitor
31
RO 0 to 19999 hours
Continued on the next page.