7. COMMUNICATION DATA LIST
IMR01Y09-E3
56
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
90
(0x005A)
Burnout direction
31
R/W 0: Upscale
1: Downscale
Valid only when the TC input and
voltage (low) input are selected.
0
91
(0x005B)
Square root extraction
31
R/W 0: Unused
1: Used
0
92
(0x005C)
Power supply frequency
31
R/W 0: 50 Hz
1: 60 Hz
If power frequency measurement was
made possible with CT input and/or
power feed forward (PFF) input applied,
set to RO (Only reading data is possible).
0
93
(0x005D)
Sampling cycle
31
R/W 0: 50 ms
1: 100 ms
2: 250 ms
1
94
(0x005E)
Remote setting input type
31
R/W 14: Current input 0 to 20 mA DC
15: Current input 4 to 20 mA DC
16: Voltage (high) input 0 to 10 V DC
17: Voltage (high) input 0 to 5 V DC
18: Voltage (high) input 1 to 5 V DC
19: Voltage (low) input 0 to 1 V DC
20: Voltage (low) input 0 to 100 mV DC
21: Voltage (low) input 0 to 10 mV DC
If changed to voltage (high) input from
current/voltage (low) input, select the
hardware by the input selector switch [for
remote setting (SR) input] at the side of the
instrument.
For the selecting procedure, see the
FB400/FB900 Instruction Manual
(IMR01W03-E )
.
15
95
(0x005F)
Digital input (DI)
assignment
31 R/W 1 to 8
See
Table 1 “Digital input (DI)
assignment” (P. 74)
.
1
96
(0x0060)
Output assignment
31
R/W 1 to 7
See
Table 2 “Output assignment”
(P. 74)
.
2
97
(0x0061)
Timer 1
31
R/W
0.0
98
(0x0062)
Timer 2
31
R/W
0.0
99
(0x0063)
Timer 3
31
R/W
0.0
100
(0x0064)
Timer 4
31
R/W
0.0 to 600.0 seconds
Customization tool is necessary when the
timer function is availed.
0.0
Continued on the next page.