7. COMMUNICATION DATA LIST
IMR01Y09-E3
47
Continued from the previous page.
ID
Name
Number
of data
items
Attri-
bute
Data range
Factory
set value
22
(0x0016)
Holding peak value ambient
temperature monitor
31 RO
−
10.0 to +100.0
°
C
23
(0x0017)
Power feed forward input
value monitor
31 RO 0.0 to 160.0 %
Display in the percentage of the load
voltage (rated value).
24
(0x0018)
Backup memory state
monitor
31 RO 0: The content of the backup memory
does not coincide with that of the
RAM.
1: The content of the backup memory
coincides with that of the RAM.
25
(0x0019)
Unused
•
•
•
32
(0x0020)
33
(0x0021)
PID/AT transfer
1, 2
31
R/W 0: PID control
1: Autotuning (AT) *
* Automatically reverts to 0 after
autotuning ends.
0
34
(0x0022)
Auto/Manual transfer
31
R/W 0: Auto mode
1: Manual mode
0
35
(0x0023)
Remote/Local transfer
31
R/W 0: Local mode
1: Remote mode
When performing remote control by
remote setting input and also performing
cascade control and ratio setting via
intercontroller communication, transfer to
the remote mode.
0
36
(0x0024)
RUN/STOP transfer
31
R/W 0: RUN mode (Control start)
1: STOP mode (Control stop)
0
37
(0x0025)
Memory area transfer
31
R/W 1 to 8
1
38
(0x0026)
Interlock release
31
R/W 0: Interlock release (execution/state)
1: Interlock
An event whose event interlock is set
to “1: Used” is set to the event ON
state results in “1: Interlocked state.”
“1” is for monitoring the interlocked
state. Under this condition, do not write
“1.”
0
1
When used in polling I/O communication, set “PID/AT transfer by polling I/O communication” in the
action mode selections (ID: 246) to “1: Valid.”
2
When PID/AT transfer is set to “1: Autotuning (AT)” in polling I/O communication, do not change any
of the other communication data for controllers with AT set until AT ends, as “1: Autotuning (AT)” may
set again when AT ends.
Continued on the next page.