~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 42 -
The relationship among the settings of F_031~F_039 is shown in the
following figure.
Note:
(1)
Base frequency > frequency at changing point 2 > frequency at
changing point 1 > start frequency.
(2) If frequency at changing point 2 < frequency at changing point 1,
frequency at changing point 2 is useless.
(3) If frequencies at changing point 1 and 2 < start frequency,
frequency at changing point 1 and 2 are useless.
(4) The F_033
、
F_035
、
F_037
、
F_039 is not confined each other.
Output
frequency
Voltage
V/F pattern
Base voltage
(F_035)
Boost voltage
(F_033)
Start voltage
(F_032)
Frequency at the
changing point 2
(F_038)
Voltage at the
changing point 1
(F_037)
Frequency at the
changing point 1
(F_036)
Voltage at the
changing point 2
(F_039)
Base frequency
(F_034)
Max. output
frequency
(F_031)