~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 54 -
(10) Settings of multiple function outputs
A.
F_058
: Output terminal Y1 setting
B.
F_059
: Output terminal Y2 setting
C.
F_060
: Settings of output terminals Ta1 and Tb1
D.
F_131
: Settings of output terminals Ta2 and Tc2
a. The outputs of the terminals Y1 and Y2 are open collector with
maximum ratings DC 48V/50mA.
b. Ta (normally open) and Tb (normally close) contacts, with
maximum ratings of AC 250V/0.5A cos =0.3.
c. ' + ' represent a contact (normally open), ' - ' represent b contact
(normally close)
d. The functions of output terminals Y1, Y2, Ta and Tb can be
programmed as followings.
0: Terminals are useless
±1: running detection (there is output once inverter is in the
running)
±2: constant speed detection (there is output once inverter is
running at constant speed.)
±3: zero speed detection running (there is output once inverter
does not output, but in the DC braking, there is no output.)
Constant speed detection (F_058=2)
Frequency setting
Frequency range for
constant speed detection
(F_061)
Time
Output Frequency
Output terminal
(Y1)
θ