~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 37 -
(2) Multiple speed level settings
A.
F_009
: Main speed with range 0.00 ~ 400.00 Hz
B.
F_010
: Speed level 1 with range 0.00 ~ 400.00 Hz
C.
F_011
: Speed level 2 with range 0.00 ~ 400.00 Hz
D.
F_012
: Speed level 3 with range 0.00 ~ 400.00 Hz
E.
F_013
: Speed level 4 with range 0.00 ~ 400.00 Hz
F.
F_014
: Speed level 5 with range 0.00 ~ 400.00 Hz
G.
F_015
: Speed level 6 with range 0.00 ~ 400.00 Hz
H.
F_016
: Speed level 7 with range 0.00 ~ 400.00 Hz
I.
F_017
:
Jog speed with range 0.00 ~ 400.00 Hz
a. The corresponding function codes
(1) Acceleration and deceleration time for multiple speed level
(F_018~F_019)
(2) Multiple function input terminal settings (F_052~F_057)
b. Production of multiple speed level
Jog
command
Multiple level
Command 3
Multiple level
Command 2
Multiple level
Command 1
ON
X
X
X
Jog speed
OFF
OFF
OFF
OFF
Main speed
OFF
OFF
OFF
ON
Speed level 1
OFF
OFF
ON
OFF
Speed level 2
OFF
OFF
ON
ON
Speed level 3
OFF
ON
OFF
OFF
Speed level 4
OFF
ON
OFF
ON
Speed level 5
OFF
ON
ON
OFF
Speed level 6
OFF
ON
ON
ON
Speed level 7
Note:
(1) ' X ' denotes " don't care ".
(2) Jog speed has the highest priority.
(3) Jog speed and multiple speed levels are determined by the status,
ON or OFF, of multiple function input terminals which are
programmed by the settings of the multiple function inputs
(F_052~F_057).
(4) ' ON ' denotes that the contact a (normally open) is short circuit
and contact b (normally close) is open. 'OFF' denotes that the
contact a (normally open) is open and contact b (normally close) is
short circuit.