~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 48 -
(9) Multiple function input terminals
A.
F_052
: Multiple function input terminal X1 setting
B.
F_053
: Multiple function input terminal X2 setting
C
.
F_054
: Multiple function input terminal X3 setting
D.
F_055
: Multiple function input terminal X4 setting
E
. F_056
: Multiple function input terminal X5 setting
F.
F_057
: Multiple function input terminal X6 setting
a. ' + ' represents contact a (normally open) and ' - ' represents
contact b (normally close)
b. Multiple function input terminals mean that the input terminals
X1~X6 can be programmed as followings:
±1: jog command (refer to the descriptions of multiple speed level)
±2: switching between the secondary acceleration and deceleration
(refer to the descriptions of multiple level acc/dec time)
±3: multiple speed levels 1 command (refer to the descriptions of
multiple speed level)
±4: multiple speed levels 2 command (refer to the descriptions of
multiple speed level)
±5: multiple speed levels 3 command (refer to the descriptions of
multiple speed level)
±6: reset command (in the fault conditions, reset command is used
to reset the inverter)
±7: external fault command (in the running, this command enables
inverter to be shutdown, and in stop, this command is useless)
±8: inhibition command for output (inhibit voltage output of
inverter)
Inhibition command for input (F_054=8)
0.3 sec
Inhibition command
for output (X3)
Run
Output voltage
Output frequency