~INSTALLATIONS AND CONFIRMATIONS~
- 8 -
S0 380V 415V 440V 460V 480V
c. Wiring diagram for
HP(200V class)/
HP(400V
class)
※
In case
as build-in brake
transistor, the mark of P1 will
change to PR.
※
For the up to 400V 40HP, there are small terminals,
on the right side of RST,
UVW, which are connected to the wire of cooling fan and
contactor. Be sure connect to the correct required voltage. (Ex.
when power is 380V, then must be connect 0 and 380V. In case
the power change to 460V, please connect to 0 and 460V)
Terminals of main circuit
3-phase power source
Forward
Vin frequency command
(DC 0~10V)
Induction motor
Grounding
Analog signal
output
(DC 0~10V)
Multi-function
output terminals
(relay output)
(AC 250V/0.5A
COS
θ
=0.3)
Multi-function
output terminals
(open collector)
(DC 48V/50mA)
RM5G/5P
R
S
T
R
S
T
FWD
REV
Tc1
Tb1
Ta1
Tc2
Ta2
M-
FM+
AM+
U
V
W
PE
P
P1
(PR)
IM
VR 1K
Ω
,1/4W
DSW1
I
V
P
P
P
Shielded
P
Terminals of control circuit
Reverse
Multi-function input terminal 1
Multi-function input terminal 2
Multi-function input terminal 3
Multi-function input terminal 4
Multi-function input terminal 5
Multi-function input terminal 6
Iin frequency command
(DC 4~20mA)
X1
X2
X3
X4
X5
X6
COM
12V(3)
Vin(2)
Iin
GND(1)
Y1
Y2
CME
Twisted-pair shielded wires
N
DC Reactor
When the DC reactor is used,
disconnect this jumper
20
~
60HP(200V)
/
25~75HP(400V)
20~60
25~75