~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 62 -
(15) DC braking
A.
F_075
:
Current of DC braking
Setting of level of current for DC braking setting with
range 0~150% of rated current of inverter.
B.
F_076
: Time interval of DC braking in stop with range 0.0~20.0
seconds.
C.
F_077
: Time interval of DC braking in start with range 0.0~20.0
seconds.
D.
F_132
: DC braking frequency in stop
Start frequency of DC braking in stop
a. The function of DC braking in stop can prevent the motor
from rotation in stop.
b. The function of DC braking in start can prevent the motor
from free running in undetermined direction ,caused by load,
in start.
If start/stop inverter by change frequency command, DC braking
enable when frequency command adjust down to F_032 start
frequency, and F_132 no effect.
DC braking
Run
Output
frequency
Time intervel of
DC braking in
start(F_077)
Time intervel of
DC braking in
stop(F_076)
DC braking
frequency in
stop(F_132)
Time