~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 68 -
Output
voltage
70%
100%
Output
frequency
Below
half load
Above
half load
Base
frequency
H.
F_094
: Selection of the overload protection of inverter (OL1)
0 : Indicate that there is no overload protection.
1 : Indicate that there is overload protection.
The overload protection of inverter
RM5G type - the time duration for 150% rated current
over 1 minute.
RM5P type - the time duration for 120% rated current
over 1 minute.
I.
F_095
: Voltage level of power source
The ranges of setting are 190.0~240.0 V for 200V class
and 340.0~480.0 V for 400V class.
Please according the power source voltage set the values,
It
influence the LE voltage level and V/F output.
J.
F_ 102
: Selection of energy saving device
0 : Do not equip energy saving device
1 : Equip energy saving device
Note: that in the condition of fan, pump or light load, this function
can save electricity.