~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 39 -
(3) Acc./dec. time of multiple speed level
A.
F_018
: Base frequency of acc./dec. with range 0.01~400.00 Hz
B.
F_019
: Primary acceleration time with range 0.0~3200.0 seconds
C.
F_020
: Primary deceleration time with range 0.0~3200.0 seconds
D.
F_021
:
Acceleration time of speed level 1 with range 0.0~3200.0
seconds
E.
F_022
: Deceleration time of speed level 1 with range 0.0~3200.0
seconds
F.
F_023
: Acceleration time of speed level 2 with range 0.0~3200.0
seconds
G.
F_024
: Deceleration time of speed level 2 with range 0.0~3200.0
seconds
H.
F_025
: Acceleration time of speed level 3 with range 0.0~3200.0
seconds
I.
F_026
: Deceleration time of speed level 3 with range 0.0~3200.0
seconds
J
.
F_027
: Secondary acceleration time with range 0.0~3200.0
seconds
K.
F_028
: Secondary deceleration time with range 0.0~3200.0
seconds
L.
F_029
: S-curve acceleration/deceleration time with range 0.0~5.0
seconds
a.
Multiple acc./dec. times are the time duration in which output
frequency is form 0 to base frequency (F_018).Multiple level
command can control the multiple speed level and acc./dec.
time of multiple speed level.
b. The acceleration/deceleration times of jog speed and speed level
4~7 are the same as those of main speed
c. Secondary acc./dec. times have the higher priority. Multiple
function input terminals can be programmed to enable
secondary acc/dec. The timing chart is shown in figure below.