~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 67 -
(21) Miscellaneous
A.
F_080
: Number of restart
Number of restart for fault conditions is 0~16.
B.
F_081
: Carry frequency setting ,The range of setting is 1~6.
The carry frequency =F_081 x 2.5 kHz.
The higher the setting is, the lower the noise is.
The carry frequency is inversely proportional to the distance
between inverter and motor.
Note: the carry frequency maximum value
RM5G TYPE 1/2HP~75HP-->Max.15KHz
Above 100HP-->Max.10KHz
RM5P TYPE 10HP~30HP-->Max.15KHz
40HP~100HP-->Max.10KHz
Above 125HP -->Max.7.5KHz
C.
F_082
: Types of stop
0 : Indicate stop by deceleration.
1 : Indicate stop by free running.
D.
F_083
: Inhibition of reversal rotation
0 : Indicate that reversal rotation is allowed.
1 : Indicate that reversal rotation is not allowed.
E.
F_091
: Fault records
Display the last 5 records of faults.
F.
F_092
: Lock of parameters
0 : Parameters are changeable. Max. frequency can not over
120.0Hz.
1 : Parameters are locked. Max. frequency can not over
120.0Hz.
2 : Parameters are changeable. Max. frequency can over
120.0Hz.
3 : Parameters are locked. Max. frequency can over
120.0Hz.
G.
F_093
: Selection of automatic voltage regulation
0 : Indicate that voltage is not regulated automatically.
1 : Indicate that voltage is regulated automatically.
Note: Connect dynamic braking unit, set the F_093(AVR)=0.