~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 59 -
(11) Frequency detection
A.
F_061
: Frequency range for constant speed detection with
range 0.0~10.0 Hz
Refer to the constant speed detection of multiple function output
terminals (Ref.Page54).
B.
F_062
: Frequency detection range with range 0.0~10.0 Hz
Refer to the frequency detection of multiple function output
terminals (Ref.Page55).
C.
F_063
: Level of frequency detection with range 0.0~400.0 Hz
Refer to the frequency detection of multiple function output
terminals (Ref.Page55).
(12) Gain of the torque boost
A.
F_064
: Gain of the automatic torque boost with range 0.0~25.5
a. This function is designed by using the automatically dynamic
voltage compensation for heavy load.
b. According to the load condition, adjust the output voltage of the
certain V/F curve for minimum current and optimal power
factor.