~DESCRIPTIONS OF FUNCTION CODE SETTINGS~
- 60 -
Level of overload
(F_068)
Time
Time interval for
overload detection (F_069)
Output terminal (Y1)
(F_058=5)
Time
Current
Time less than overload
detection time (F_069)
(13) Settings of overload detection
A.
F_065
: Selection of overload detection (OLO)
0 : There is no output for overload detection.
1 : There is output for overload detection.
B
. F_066
: Status of overload detection (OLO)
0 : There is output for the condition of constant frequency
only.
1 : There is output for inverter running.
C.
F_067
: Output setting for overload (OLO)
0 : Inverter is still running after that overload has been
detected.
1 : Output of inverter is inhibited after that overload has
been detected.
D.
F_068
: Level of overload setting (OLO)
The range of setting is 30~200% of rated current of inverter.
E.
F_069
: Time interval for overload detection
The time interval, in which the output current is greater than the
setting of F_068, is required for overload detection. The range of
setting is 0.1~10.0 seconds.
a. The function of overload detection is shown in the timing chart
b. The time interval in which the overload is occurred greater than
time interval for overload detection, the overload is then
detected and keypad displays '
'
c. In the running, the overload is detected during the running
interval.
d. After overload, the inverter does output or not in according with
the F_067 setting.
e. The primary purpose of overload detection is to protect system
from damage so that the level and time interval of overload
detection are determined by application.