LIST OF FUNCTION CODE SETTING~
- 28 -
Function
Name
Descriptions
Range of
setting
Resolu-
tion
Factory
setting
No. page
reference
for detail
F_044
Selection of
FM+ analog
output signal
0:
Analog signal indicates output frequency
1
:Analog signal indicates frequency command
2
:Analog signal indicates output current
3:
Analog signal indicates Vin frequency command
4:
Analog signal indicates Iin frequency command
0~4
—
0
46
F_045 FM+ analog
output gain
Gain=max output frequency/output frequency.
Or Gain=rated current of inverter/output current
0.00~2.00
0.01
1.00 46
F_046
Overload
protection
selection
0:No overload protection for motor
1:Overload protection for motor
2:Overload protection for motor with
independence heat fan
0~2
—
1
47
F_047 Reserved
Reserved
—
—
0
47
F_048 Rated current
of motor
According to the spec. of motor
10~150%
by the inverter
rated current
0.1A
According
to the spec.
of motor
47
F_049
No-load current
of motor
According to the spec. of motor
0~motor
rated current
0.1A
1/3 motor
rated
current
47
F_050
Slip
compensation
According to the load condition, slip is
compensation for constant speed
-9.9~10.0
0.1HZ
0.0
47
F_051
No. poles of motor
Setting of poles of motor for conversion of RPM
2~10
2P
4P
47
F_052 Input terminal
X1 setting
3
F_053 Input terminal
X2 setting
4
F_054 Input terminal
X3 setting
1
F_055 Input terminal
X4 setting
2
F_056 Input terminal
X5 setting
7
F_057 Input terminal
X6 setting
X1=0:UP/DOWN
command enter key
X2=0:DC braking
enable (stop)
X3=0:current limit
enable
X4=0:primary and
secondary speed
select
X5=0
:
stop command
with 3-line sustaining
circuit (contact a)
X6=0
:
stop command
with 3-line sustaining
circuit (contact b)
±1:jog command
±2:switch between the
secondary acceleration and
deceleration
±3:multiple speed level 1
command
±4:multiple speed level 2
command
±5:multiple speed level 3
command
±6:reset command
±7:external fault command
±8:inhibition command for
output
±9:stop in free running
±10:speed search from the
maximum frequency
±11:speed search from the set
frequency
±12:inhibition command for
acceleration and deceleration
±13:up command
±14:down command
±15:clear up/down frequency
command
±16:select analog input source
-16~ +16
(Re.9)
—
6
48
F_058
Output terminal
Y1 setting
3
F_059
Output terminal
Y2 setting
2
F_060
Settings of
output
terminals Ta1
and Tb1
0
: useless
±1:running detection
±2:constant
speed detection
±3:zero speed detection
±4:frequency detection
±5:overload detection
±6:stall
prevention detection
±
7:under voltage detection
±8:detection of braking
±9:detection of restart after
instantaneous
power interruption
±10:detection of restar
after fault conditions
±11:detectionof fault conditions
-11~+11
(Re.9)
—
11
54
F_061
Frequency
range for
constant speed
detection
Frequency range for constant speed detection
0.0~10.0
0.1HZ
2.0
59
F_062
Frequency
detection range Frequency detection range
0.0~10.0
0.1HZ
2.0
59
F_063
Level of frequency
detection
Level of frequency detection for multiple
function output terminal
0.0~400.0
0.1HZ
0.0
59
The color as means which can be set during operation.