Appendix F: Additional PXE Information
356
Assumption:
Upper Warning threshold is enabled.
Upper Warning = 20 (degrees Celsius)
Deassertion Hysteresis = 3 (degrees Celsius)
"Deassertion" level = 20-3 = 17 (degrees Celsius)
When the PXE detects that a temperature sensor's reading drops below
20 degrees Celsius, moving from the "above upper warning" range to the
"normal" range, either of the following may occur:
If the temperature falls between 20 and 17 degrees Celsius, the
"de-assert" action is NOT turned on.
If the temperature drops to 17 degrees Celsius or lower, the PXE
turns on the "de-assert" action to announce the end of the "above
upper warning" state.