Chapter 7: Using SNMP
186
2. Select the "enable" checkbox in the "SNMP v1 / v2c" field to enable
communication with an SNMP manager using SNMP v1 or v2c
protocol.
Type the SNMP read-only community string in the Read
Community String field. Usually the string is "public."
Type the read/write community string in the Write Community
String field. Usually the string is "private."
3. Select the "enable" checkbox in the "SNMP v3" field to enable
communication with an SNMP manager using SNMP v3 protocol.
Tip: You can permit or disallow a user to access the PXE via the
SNMP v3 protocol. See
Configuring Users for Encrypted SNMP
v3
(on page 186).
4. Enter the MIB-II system group information, if applicable:
a. sysContact - the contact person in charge of the system being
contacted
b. sysName - the name assigned to the system
c. sysLocation - the location of the system
5. Select the MIB to be downloaded. The SNMP MIB for your PXE is
used by the SNMP manager.
Important: You must download the SNMP MIB for your PXE to use
with your SNMP manager. Click Download MIB in this dialog to
download the desired MIB file. For more details, see
Downloading
SNMP MIB
(on page 188).
6. Click
OK.
Configuring Users for Encrypted SNMP v3
The SNMP v3 protocol allows for encrypted communication. To take
advantage of this, users need to have an Authentication Pass Phrase
and Privacy Pass Phrase, which act as shared secrets between them
and the PXE.
To configure users for SNMP v3 encrypted communication:
1. Choose User Management > Users. The Manage Users dialog
appears.
2. Select the user by clicking it.
3. Click Edit or double-click the user. The Edit User 'XXX' dialog
appears, where XXX is the user name.
4. To change the SNMPv3 access permissions, click the SNMPv3 tab
and make necessary changes. For details, see Step 6 of
Creating a
User Profile
(on page 78).
Содержание PXE
Страница 1: ...Copyright 2014 Raritan Inc PXE 0C v3 0 E August 2014 255 80 0008 00 Raritan PXE User Guide Release 3 0...
Страница 12: ...Contents xii To Assert and Assertion Timeout 352 To De assert and Deassertion Hysteresis 354 Index 357...
Страница 16: ......
Страница 50: ...Chapter 5 Using the PDU 34 4 Pull up the operating handle until the colorful rectangle or triangle turns RED...
Страница 200: ...Chapter 6 Using the Web Interface 184 10 To print the currently selected topic click the Print this page icon...
Страница 339: ...Appendix A Specifications 323 RS 485 Pin signal definition al 4 5 6 D bi direction al Data 7 8...
Страница 353: ...Appendix D LDAP Configuration Illustration 337 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 380: ...Index 364 Z Zero U Products 1...
Страница 381: ......