![Peaco Support 2S-0.5G-B Скачать руководство пользователя страница 90](http://html.mh-extra.com/html/peaco-support/2s-0-5g-b/2s-0-5g-b_user-manual_1517001090.webp)
-89-
Chapter 6 Description of Function Codes
When AI is used as the frequency setting source, the corresponding value 100% of the volta-
ge/current input corresponds to the value of F06.
5: Pulse setting (HDI)
The frequency given is given by the terminal pulse. Pulse given signal specifications: voltage
range 9V~26V, frequency range 0kHz~100kHz. Pulse given can only be input from the multi-
function input terminal HDI. The relationship between the input pulse frequency of the HDI
terminal and the corresponding setting is set through F06.33~F06.36. The corresponding
relationship is a straight line corresponding relationship between 2 points. The 100.0% set
corresponding to the pulse input is relative to the maximum frequency F00 .03 percent.
6: Multi-reference
In multi-reference mode, combinations of different input terminal states correspond to differ-
ent set frequencies by setting F06 and F12. The supports a maximum of 16 speeds implem-
ented by 16 state combinations of four terminals in Group F12.
The multiple references indicate percentages of the value of F00.03 (Maximum frequency).
If a S terminal is used for the multi-reference function, you need to perform related setting in
group F06.
7: Simple PLC
When the simple programmable logic controller (PLC) mode is used as the frequency sourc-
e, the running frequency of the AC drive can be switched over among the 16 frequency refe-
rences. You can set the holding time and acceleration/deceleration time of the 16 frequency
references. For details, refer to the descriptions of Group F12.
8: PID
The output of PID control is used as the running frequency. PID control is generally used in
on-site closed-loop control, such as constant pressure closed-loop control and constant
tension closed-loop control.
When applying PID as the frequency source, you need to set parameters of PID function in
group F10.
9: Communication setting
The main frequency source is set by means of communication.For details,see the description
of Appendix A Serial Communications.
10: Potentiometer
The frequency is set by potentiometer.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F00.07
Frequency B
command selection
Same as F00.06