Chapter 6 Description of Function Codes
-175-
setting value
output frequency
feedback
deviation limit
time
time
Fig.6-29 Relation between
deviation limit and output frequency
Function
code
Name
Description
(setting range)
Factory
Default
Change
F10.10
PID differential limit
0.00%
~
100.00%
0.10%
※
It is used to set the PID differential output range. In PID control, the differential operation may
easily cause system oscillation. Thus, the PID differential regulation is restricted to a small
range.
The PID setting change time indicates the time required for PID setting changing from 1.1%
to 100.0%. The PID setting changes linearly according to the change time, reducing the imp-
act caused by sudden setting change on the system.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F10.11
PID setting change time
0.00
~
650.00s
0.00s
※
Function
code
Name
Description
(setting range)
Factory
Default
Change
F10.12
PID feedback filter time
0.00
~
60.00s
0.00s
※
F10.13
PID output filter time
0.00
~
60.00s
0.00s
※
C
h
a
p
te
r
6
Peaco Support FC280 Series VFD User Manual