Function
code
Name
Description
(setting range)
Factory
Default
Change
F05.54
Short-circuit to ground
upon power-on
0: Disabled
1: Enabled
1
●
F05.55
Output terminal action
during fault auto reset
0: Not act
1: Act
0
●
F05.56
Backup frequency
upon abnormality
0.0%
~
100.0%
(100.0% corresponding to
maximum frequency)F00.03)
100.0%
●
F05.57
Type of motor
temperature sensor
0: No temperature sensor
1: PT100
2: PT1000
0
●
F05.58
Motor overheat
protection threshold
0℃
~
200℃
100℃
●
F05.59
Motor overheat
warning threshold
0℃
~
200℃
90℃
●
F05.60
Action pause judging
voltage at
instantaneous power
failure
F05.04
~
100.0%
90.0%
●
Group F06: Input Terminals
F06.00
S1 terminal function
selection
0: no function
1: forward run
2: reverse run
3: 3-wire operation control
4: forward jog
5: reverse jog
6: coast to stop
7: fault reset
8: external fault normal open
input
9: UP command
10: DOWN command
11: clear UP/ DOWN
(
terminal
、
keypad
)
12: multi-speed terminal 1
13: multi-speed terminal 2
14: multi-speed terminal 3
1
●
F06.01
S2 terminal function
selection
2
●
F06.02
S3 terminal function
selection
4
●
F06.03
S4 terminal function
selection
6
●
F06.04
S5 terminal function
selection
12
●
F06.05
S6 terminal function
selection
13
●
F06.06
S7 terminal function
selection
0
●
Chapter 5 Function & Parameter Table
-60-
C
h
a
p
te
r
5
Peaco Support FC280 Series VFD User Manual