-71-
Chapter 5 Function & Parameter Table
Function
code
Name
Description
(setting range)
Factory
Default
Change
F09.05
Deceleration time 4
0.0s
~
6500.0s
Model
dependent
※
F09.06
JOG running frequency
0.00Hz
~
F00.03( max.
frequency)
2.00Hz
※
F09.07
JOG acceleration time
0.0s
~
6500.0s
20.0s
※
F09.08
JOG deceleration time
0.0s
~
6500.0s
20.0s
※
F09.09
Jump frequency 1
0.00Hz
~
F00.03( max.
frequency)
0.00Hz
※
F09.10
Jump frequency 2
0.00Hz
~
F00.03( max.
frequency)
0.00Hz
※
F09.11
Frequency jump amplitude
0.00Hz
~
F00.03( max.
frequency)
0.00Hz
※
F09.12
Forward/Reverse rotation
dead-zone time
0.0s
~
3000.0s
0.0s
※
F09.13
Reverse control
0: enabled
1: disabled
0
※
F09.14
Running mode when set
frequency lower than
frequency lower limit
0:run at frequency
lower limit
1: stop
2: run at zero speed
0
※
F09.15
Accumulative power-on time
threshold
0.0s
~
6500.0s
0h
※
F09.16
Accumulative running time
threshold
0.0s
~
6500.0s
0h
※
F09.17
Startup protection
0: No
1: Yes
0
※
F09.18
Droop control
0.00Hz
~
10.00Hz
0.00Hz
※
F09.19
Motor switchover
0: Motor 1
1: Motor 2
0
●
F09.20
Frequency detection value(
FDT1)
0.00Hz
~
F00.03( max.
frequency)
50.00Hz
※
F09.21
Frequency detection
hysteresis (FDT hysteresis 1)
0.0%
~
100.0%
(
FDT1
level
)
5.0%
※
F09.22
Frequency detection value(
FDT2)
0.00Hz
~
F00.03( max.
frequency)
50.00Hz
※
F09.23
Frequency detection
hysteresis (FDT hysteresis 2)
0.0%
~
100.0%( FDT2
level)
5.0%
※
C
h
a
p
te
r
5
Peaco Support FC280 Series VFD User Manual
www.peacosupport.com [email protected] Free Shipping Worldwide Reliable Supplier
PEACO SUPPORT