Chapter 6 Description of Function Codes
Group F00: Standard Function Parameters
0: non- PG vector control
(
SVC
)
It indicates open-loop vector control, and is applicable to high-performance control applicatio-
ns without encoder such as machine tool, centrifuge, wire drawing machine and injection
moulding machine. One AC drive can operate only one motor.
1: PG vector control
(
FVC
)
It is applicable to high-accuracy speed control or torque control applications such as high-
speed paper making machine, crane and elevator. One AC drive can operate only one
motor. An encoder must be installed at the motor side, and a PG card matching the encoder
must be installed at the AC drive side.
2: V/F control
It is applicable to applications with low load requirements or applications where one AC drive
operates multiple motors, such as fan and pump.
Note:
If vector control is used, motor self-learning must be performed because the advantag-
es of vector control can only be utilized after correct motor parameters are obtained.Better
performance can be achieved by adjusting speed regulator parameters in group F03 (or gro-
ups F15 for motor 2).
Function
code
Name
Description
(setting range)
Factory
Default
Change
F00.00
Speed control mode
0: non-PG vector control (SVC
)
1: PG vector control
(
FVC
)
2: V/F control
2
●
Function
code
Name
Description
(setting range)
Factory
Default
Change
F00.01
Command source
selection
0:keypad control
1:terminal control
2:RS 485 communication control
0
※
It is used to determine the input channel of the AC drive control commands, such as run, stop,
forward rotation, reverse rotation and jog operation. You can input the commands in the
following three channels:
0: keypad control
Commands are given by pressing keys RUN,STOP/RES on the keypad.
1: terminal control
Commands are given by means of multifunctional input terminals with functions such as FWD,
REV, forward JOG, and reverse JOG.