Function
code
Name
Description
(setting range)
Factory
Default
F16.09
Water level
threshold
The unit is percentage, 0.0~100.0% When
the detected water level control analog
signal is greater than the water level
threshold, and continues this state after
the delay time of F16.10, it reports full
water early warning (FULL) and sleeps. If
it is non-continuous, that is, when the
delay time does not arrive, the given
analog signal is greater than the water
level threshold, and the delay time is
automatically cleared. Then, when the
measured water level control analog signal
is less than the water level threshold, the
delay time
is restarted.
70.00%
F16.10
Full water level
delay
0~60000s Full water delay time setting.
60s
F16.11
Empty water level
delay
0~60000s Empty water delay time setting.
In the state of full water warning, when the
detected water level control analog signal
is less than the F16.09 water level
threshold, the delay time is started. After
this delay time of F16.11 continues, the full
water warning is cleared and the system
returns to normal. . In non-continuous
situations,
the delay timer is automatically
cleared.
600s
F16.12
Underload detection
current
0.0%: Underload not detected When not
0.0%, it is determined by the parameter
setting value of F16.12. 100.0%
corresponds to the rated current of the
motor. If the current value continues to be
less than the set value of F16.12, after the
F16.13 pump underload running time,
underload warning will be reported,
otherwise it will work normally. In non-
continuous situations, the delay timer is
automatically cleared.
50%
-216-