![Peaco Support 2S-0.5G-B Скачать руководство пользователя страница 76](http://html.mh-extra.com/html/peaco-support/2s-0-5g-b/2s-0-5g-b_user-manual_1517001076.webp)
-75-
Chapter 5 Function & Parameter Table
Function
code
Name
Description
(setting range)
Factory
Default
Change
F10.03
PID output characteristic
selection
0: PID output is positive
characteristic
1: PID output is negative
characteristic
0
※
F10.04
PID setting feedback range
0.0
~
1000.0
10.0
※
F10.05
Proportional gain Kp1
0.0
~
100.0
20.0
※
F10.06
Integral time Ti1
0.01s
~
10.00s
2.00s
※
F10.07
Differential time Td1
0.000s
~
10.000s
0.000s
※
F10.08
Cut-off frequency of PID
reverse rotation
0.00
~
F00.03( maximum
frequency )
0.00Hz
※
F10.09
PID deviation limit
0.0%
~
100.0%
0.0%
※
F10.10
PID differential limit
0.00%
~
100.00%
0.10%
※
F10.11
PID setting change time
0.00
~
650.00s
0.00s
※
F10.12
PID feedback filter time
0.00
~
60.00s
0.00s
※
F10.13
PID output filter time
0.00
~
60.00s
0.00s
※
F10.15
Proportional gain Kp2
0.0
~
100.0
20.0
※
F10.16
Integral time Ti2
0.01s
~
10.00s
2.00s
※
F10.17
Differential time Td2
0.000s
~
10.000s
0.000s
※
F10.18
PID parameter switchover
condition
0: No switchover
1: Switchover via input
terminal
2: Automatic switchover
based on deviation
0
※
F10.19
PID parameter switchover
deviation 1
0.0%
~
F10.20
20.0%
※
F10.20
PID parameter switchover
deviation 2
F10.19
~
100.0%
80.0%
※
F10.21
PID initial value
0.0%
~
100.0%
0.0%
※
F10.22
PID initial value holding time 0.00
~
650.00s
0.00s
※
F10.23
Maximum deviation between
two PID outputs in forward
direction
0.00%
~
100.00%
1.00%
※
C
h
a
p
te
r
5
Peaco Support FC280 Series VFD User Manual