Chapter 6 Description of Function Codes
Any current
reaching
Any current reaching
detection signal
MD1 or relay
ON
OFF
OFF
OFF
Any current
reaching amplitude
t
Output current
ON
Any current
reaching amplitude
Fig.6-27 Any current reaching detection
Function
code
Name
Description
(setting range)
Factory
Default
Change
F09.43
Timing function
0: Disabled
1: Enabled
0
※
F09.44
Timing duration
source
0: F09.45
1: analog AI1
2: analog AI2
3: analog AI3
(Analog input range corresponds to
F09.45)
0
※
F09.45
Timing duration
0.0Min
~
6500.0Min
0.0Min
※
These parameters are used to implement the AC drive timing function.
If F09.43 is set to 1, the AC drive starts to time at startup. When the set timing duration is
reached, the AC drive stops automatically and meanwhile the corresponding multi-function
terminal output becomes ON.
The AC drive starts timing from 0 each time it starts up and the remaining timing duration.
The timing duration is set in F09.44 and F09.45, in unit of minute.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F09.46
AI1 input voltage lower limit 0.00V
~
F09.47
3.10V
※
F09.47
AI1 input voltage upper limit F09.46
~
10.00V
6.80V
※
-166-
C
h
a
p
te
r
6
Peaco Support FC280 Series VFD User Manual