![Peaco Support 2S-0.5G-B Скачать руководство пользователя страница 54](http://html.mh-extra.com/html/peaco-support/2s-0-5g-b/2s-0-5g-b_user-manual_1517001054.webp)
Function
code
Name
Description
(setting range)
Factory
Default
Change
F03.24
Torque setting mode
selection
7:MAX(AI1,AI2)
(corresponding to F03.26
digital setting)
0
※
F03.26
Torque setting by
keypad
-200.0%
~
200.0%
105%
※
F03.28
Upper frequency limit of
forward when torque
control
0.00Hz
~
F00. 03(max.
frequency)
50.00Hz
※
F03.29
Upper frequency limit of
reverse when torque
control
0.00Hz
~
F00. 03(max.
frequency)
50.00Hz
※
F03.30
Torque control
acceleration time
0.00s
~
650.00s
0.00s
※
F03.31
Torque control
deceleration time
0.00s
~
650.00s
0.00s
※
Group F04: V/F Control Parameters
F04.00
Motor1 V/F curve setting
0: linear V/F
1: multi-point V/F
2: square V/F
3: V/F complete seperation
4: V/F half seperation
5:1.2 square V/F
6: 1.4 square V/F
7: 1.6 square V/F
8: 1.8 square V/F
0
※
F04.01
Motor 1 torque boost
0.0%:( auto torque boost)
0.1%
~
30.0%
Model
dependent
●
F04.02
Cut-off frequency of
motor 1 torque boost
0.00Hz
~
F00.03
( max.frequency)
50.00Hz
●
F04.03
Motor1 V/F frequency
point 1
0.00Hz
~
F04.05
0.00Hz
●
F04.04
Motor1 V/F voltage
point 1
0.0%
~
100.0%
0.0%
●
F04.05
Motor1 V/F frequency
point 2
F04.03
~
F04.07
0.00Hz
●
-53-
Chapter 5 Function & Parameter Table
C
h
a
p
te
r
5
Peaco Support FC280 Series VFD User Manual
www.peacosupport.com [email protected] Free Shipping Worldwide Reliable Supplier
PEACO SUPPORT