Chapter 6 Description of Function Codes
-179-
Function
code
Name
Description
(setting range)
Factory
Default
Change
F10.26
Detection value of PID
feedback loss
0.0%: Not judging feedback
loss 0.1%–100.0%
0.0%
※
F10.27
Detection time of PID
feedback loss
0.0s
~
20.0s
0.0s
※
These parameters are used to judge whether PID feedback is lost.
If the PID feedback is smaller than the value of F10.26 and the lasting time exceeds the
value of F10.27, the AC drive reports E02E and acts according to the selected fault
protection action.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F10.28
PID operation at stop
0: No PID operation at stop
1: PID operation at stop
0
※
It is used to select whether the PID continues to operate in the PID stop state. In general
applications, the PID should stop computing in the stop state.