6: Simple PLC
If the voltage source is simple PLC mode, parameters in group F12 must be set to determine
the setting output voltage.
7: PID control
The output voltage is generated based on PID closed loop. For details, see the description of
PID in group F10.
8: Rs485 communication
The output voltage is set by the host computer by means ofcommunication.
The voltage source for V/F separation is set in the same way as the frequency source. When
the above voltage source is selected from 1 to 8, 0 to 100% corresponds to the output power
0V to the rated voltage of the motor.
-119-
Chapter 6 Description of Function Codes
The rise time of V/F separation refers to the time required for the output voltage to change
from 0V to the rated voltage of the motor. As shown in Figure 6-8:
Function
code
Name
Description
(setting range)
Factory
Default
Change
F04.15
Voltage digital setting for
V/F separation
0.0s
~
1000.0s
note: time from 0V to motor
rated voltage (F02.04)
0.0s
※
t
1
Actual voltage
rising time
Set voltage rising time
Output voltage
Rated motor voltage
Set voltage declining time
Actual voltage
declining time
Target voltage
t
2
Fig.6-8
Voltage of V/F separation
C
h
a
p
te
r
6
Peaco Support FC280 Series VFD User Manual