Chapter 6 Description of Function Codes
Function
code
Name
Description
(setting range)
Factory
Default
Change
F10.23
Maximum deviation
between two PID outputs
in forward direction
0.00%
~
100.00%
1.00%
※
F10.24
Maximum deviation
between two PID outputs
in reverse direction
0.00%
~
100.00%
1.00%
※
F10.23 and F10.24 respectively correspond to the maximum absolute value of the output de-
viation in forward direction and in reverse direction.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F10.25
PID integral property
Unit's digit :Integral
separated
0: Invalid
1: Valid
Ten's digit :Whether to stop
integral operation when the
output reaches the limit
0: Continue integral
operation
1: Stop integral operation
00
※
Integral separated
:
If it is set to valid, , the PID integral operation stops when the multi-
function digital S allocated with function 22 "PID integral pause" is ON In this case, only pro
-
portional and differential
operations take effect.
If it is set to invalid, integral separated remains invalid no matter whether the S allocated with
function 22 "PID integral pause" is ON or
not.
Whether to stop integral operation when the output reaches the limit. If "Stop integral opera
-
tion" is selected, the PID integral operation stops, which may help to reduce the PID
oversh
-
oot.
-178-