Chapter 6 Description of Function Codes
0: Decelerate to stop
After the stop command is enabled, the AC drive decreases the output frequency according to
the deceleration time and stops when the frequency decreases to zero.
1: Coast to stop
After the stop command is enabled, the AC drive immediately stops the output. The motor will
coast to stop based on the mechanical inertia.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F01.08
Stop mode
0: deceleration to stop
1:stop freely
0
●
During the process of decelerating to stop, the AC drive starts DC braking when the running
frequency is lower than the value.
When the running frequency decreases to the initial frequency of stop DC braking, the AC
drive stops output for a certain period and then starts DC braking. This prevents faults such
as overcurrent caused due to DC braking at high speed.
This parameter specifies the output current at DC braking and is a percentage relative to the
base value. The larger current ,the effect of DC brake is higher, and heat of motor and Ac
drive is higher.
This parameter specifies the holding time of DC braking. If it is set to 0, DC braking is cancel-
led.
The stop DC braking process is shown in the following figure 6-4.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F01.09
Initial frequency of
stop DC braking
0.00Hz
~
F00.03( max.
frequency)
0.00Hz
●
F01.10
Waiting time of stop
DC braking
0.0s
~
100.0s
0.0s
※
F01.11
Stop DC braking
current
0%
~
100%
0.0%
●
F01.12
Stop DC braking time
0.0s
~
100.0s
0.0s
—