Chapter 6 Description of Function Codes
If F05.18 (Detection time of too large speed deviation) is 0.0s, this function is disabled.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F05.19
Fault auto reset times
0
~
20
0
※
Function
code
Name
Description
(setting range)
Factory
Default
Change
F05.20
Time interval of fault auto
reset
0.1s
~
100.0s
1.0s
※
It is used to set the times of fault auto resets if this function is used. After the value is excee
-
ded, the AC drive will remain in the fault
state.
It is used to set the waiting time from the alarm of the AC drive to fault auto reset.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F05.21
Fault
protection
action
selection 1
Unit's digit:motor overload
(
E007
)
0:coast to stop
1:stop according to the stop mode
2:continue to run
Ten's digit :power input phase loss (E012)
Hundred's digit:power output phase loss
(E013)
Thousand's digit:external equipment
fault(E00d)
Ten thousand's digit:communication
fault(E018)
00000
※
F05.22
Fault
protection
action
selection 2
Unit's digit:encoder/PG card fault(E026)
0:coast to stop
Ten's digit:EEPROM read-write
fault(E021)
0:coast to stop
1:stop according to the stop mode
Hundred's digit: reserved
Thousand's digit: motor overheat(E036)
00000
※