Function
code
Name
Description
(setting range)
Factory
Default
Change
F06.14
Terminal UP/DOWN
rate
0.001Hz/s
~
65.535Hz/s
1.00Hz/s
※
-139-
Chapter 6 Description of Function Codes
It is used to adjust the rate of change of frequency when the frequency is adjusted by means
of terminal UP/DOWN.
l
If F00.11 (Frequency reference resolution) is 2, the setting range is 0.001–65.535Hz/s.
l
If F00.11 (Frequency reference resolution) is 1, the setting range is 0.01–655.35Hz/s.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F06.15
S1 delay time
0.0s
~
3600.0s
0.0s
●
F06.16
S2 delay time
0.0s
~
3600.0s
0.0s
●
F06.17
S3 delay time
0.0s
~
3600.0s
0.0s
●
These parameters are used to set the delay time of the AC drive when the status of S termin
-
als changes.
Currently, only S1, S2 and S3 support the delay time function
.
These parameters are used to define the relationship between the analog input voltage and
the corresponding setting. When the analog input voltage exceeds the maximum value
(F06.20), the maximum value is used. When the analog input voltage is less than the minim
-
um value (F06.08), the value set in F06.39 (Setting for AI less than minimum input) is used.
When the analog input is current input, 1 mA current corresponds to 0.5 V voltage.
F06.22 (AI1 filter time) is used to set the software filter time of AI1. If the analog input is liable
to interference, increase the value of this parameter to stabilize the detected analog input.
Function
code
Name
Description
(setting range)
Factory
Default
Change
F06.18
AI1 lower limit
0.00V
~
F06.20
0.00V
※
F06.19
Corresponding setting
of AI1 lower limit
-100.0%
~+
100.0%
0.0%
※
F06.20
AI1 upper limit
F06.18
~+
10.00V
10.00V
※
F06.21
Corresponding setting
of AI1 upper limit
-100.0%
~+
100.0%
100.0%
※
C
h
a
p
te
r
6